Simplex 49VOH-APPLC-O — TrueAlert ES weatherproof ceiling-mount visible only strobe, clear lens, appliance only.
Visible only appliances on a Simplex IDNAC signalling line circuit are individually powered, addressed and controlled from the panel, so each strobe reports its own point ID, custom label, type and candela setting back to the control unit. The circuit holds a regulated 29 VDC even on battery standby, letting the strobe run at lower current. This part is the appliance alone; cover and back box are ordered separately.
- Multi-candela LED strobe: W110, W135 and W185 settings plus a 110 cd setting
- Maximum RMS current 298 mA, 330 mA, 393 mA and 250 mA respectively
- Special application 23 VDC to 30 VDC; 1 Hz flash rate
- UL/ULC rating -40°F to 151°F (-40°C to 66°C) at the W settings
- In/out terminals for 18 AWG to 12 AWG
- Magnet test and Self-Test reporting at the panel
Pair it with a 49VOC series cover (49VOC-CRF-O red FIRE, 49VOC-CWF-O white FIRE, plus ALERT, FEU and logo variants) and a 49WPBB-VOCR or 49WPBB-VOCW back box. Do not confuse it with the audible/visible 49AVH-APPLC-O.