Simplex 4007-9101 — 4007ES Hybrid fire detection and control unit, red cabinet, with one addressable SLC and four conventional notification appliance circuits.
Hybrid refers to initiation: the panel takes addressable devices on its IDNet 2 channel and conventional two-wire zones on plug-in zone/relay modules, while driving non-addressable horns and strobes. That mix moves a conventional building onto an addressable head end without rewiring.
- IDNet 2 SLC, 100 addressable points, expandable to 250 with two 4007-9803 modules
- Four NACs, each selectable Class A or Class B, 6 A total output power
- Input 120 VAC, 2 A maximum at 102 to 132 VAC, 50/60 Hz
- Ships with one 4007-9801 eight-point zone/relay module; four maximum
- 4.3 in. color touchscreen; battery charging 6.2 Ah through 33 Ah
- 145 mA supervisory, 190 mA alarm; 32°F to 120°F; NEMA 1 and IP30
The 4007-9102 is the same unit in a platinum cabinet, and 4007-9101BA marks a USA-assembled build, not a different panel. The 4007ES panels on data sheet S4007-0002 use addressable notification instead of these conventional NACs.