Fireray 3000-209 — controller back box for the FFE Fireray 3000 end-to-end infrared optical beam smoke detector.
The Fireray 3000 pairs separate transmitter and receiver heads with one low-level control unit carrying the LCD display, sensitivity settings and the fire and fault relays. The 3000-209 is the enclosure that control unit sits in, so the optics stay high in an atrium or warehouse while set-up and testing stay within reach. FFE lists it in the Fireray 3000 ordering information as the controller back box.
- FFE ordering code 3000-209, Fireray 3000 Controller Back Box
- Houses the control unit, 7.99 × 4.88 × 2.81 in. (W × H × D), 1.34 lb
- Control unit runs on 12 to 36 VDC, 14 mA constant with one or two receivers
- Receiver-to-controller link is 18–14 AWG twisted jacketed pair, up to 330 ft (100 m)
- 3000-210 semi-flush trim plate is the matching recessed-install accessory
Check the code before buying. 3000-210 is only a trim plate. 5000-011 is the surface-mount back box for the detector heads, not the controller, and needs one 3000-202 adaptor per head. 3000-203 is a 4 in. square cover plate. Only 3000-209 is the controller enclosure.