Fire-Lite SD365 is a white, low-profile intelligent plug-in photoelectric smoke detector for Fire-Lite addressable fire alarm control panels. It operates in LiteSpeed protocol only and is addressed with rotary decimal switches. The SD365 Series is a direct replacement for the SD355 Series.
An enhanced optical sensing chamber detects smoke from a wide range of combustion sources and is designed to meet UL 268 7th Edition. Point ID addressing gives responders the exact detector location. Two LEDs blink when the panel polls the unit and latch on in alarm. The cover and insect-resistant screen come off for field cleaning, and a built-in functional test switch is operated with an external magnet. Sensitivity can be tested from the panel as required by NFPA 72.
Specifications
| Model |
SD365 (white) |
| Protocol |
LiteSpeed only |
| Sensitivity |
UL: 0.5% to 4.0% per foot obscuration; ULC: 0.5% to 3.5% per foot |
| Factory preset |
1.5% nominal |
| Voltage range |
15 - 32 volts DC peak |
| Standby current |
200 µA @ 24 VDC (one communication every 5 seconds, LED enabled) |
| Maximum current |
4.5 mA @ 24 VDC (“ON”) |
| Operating temperature |
32°F to 122°F (0°C to 50°C) |
| Humidity |
10% - 93% non-condensing |
| Certified velocity range |
0 - 4000 ft/min, suitable for installation in ducts |
| Size |
2.0″ high; B300-6 base 6.1″ diameter, B501 base 4″ |
| Shipping weight |
3.4 oz. (95 g) |
| Certifications |
UL/ULC S1059; FM Approved; CSFM 7272-0075:0502 |
| Spacing |
30 feet in low airflow with smooth ceiling, per NFPA 72 |
Compatibility
-
LiteSpeed only: the white SD365 is not the correct part if the loop must run CLIP. The ivory version, SD365-IV, operates in both CLIP and LiteSpeed modes.
-
Replaces SD355: the SD365 is a direct replacement for the SD355 Series, and the separate base allows interchange of photoelectric, ionization and thermal sensors.
-
No end-of-line resistors: the SLC loop is supervised. T-taps are permitted for Style 4 (Class B) wiring only.
-
Bases: B300-6 (6″) and B501 (4″); relay, isolator and sounder bases are also available. See installation sheet I56-3626 for device limits between isolator modules and isolator bases.
Related models
-
SD365T - white, adds a 135°F (57°C) fixed-temperature thermal device; 32°F to 100°F operating range
-
SD365R - white, remote test capable, for DNR/DNRW duct smoke detector housings
-
SD365A - same as SD365 but with ULC certification
Specifications from the Fire•Lite Alarms data sheet “SD365 Series Addressable Photoelectric Smoke Detectors,” DF-61010:B (2019). Manufacturer specifications are subject to change without notice.
Documents
FAQ
Does the SD365 include a base?
No. The sensor base is supplied separately; the SD365 installs in a B300-6 (6.2 in. diameter installed) or B501 (4.1 in.) base.
Will the SD365 work on a CLIP loop?
No. The white SD365 supports LiteSpeed protocol only. The ivory SD365-IV supports either LiteSpeed or CLIP.
Can it be used in a duct?
Yes. The SD365 is UL 268A certified for duct applications with an air velocity rating of 0 to 4000 ft/min, and intelligent photoelectric sensors are also certified for use inside DNR(W) duct housings.
How is the SD365 tested?
A test magnet (M02-04-01 or M02-09-00) simulates smoke for a functional test, sensitivity readings are available through the panel, and approved canned smoke agents can be used for smoke entry testing.