Fire-Lite SD365T — white low-profile addressable photoelectric smoke detector with a built-in 135 °F (57 °C) fixed-temperature thermal device, LiteSpeed protocol only.
The head plugs into a separate base on the two-wire signalling line circuit and carries its own address, set on rotary decimal switches, so the panel reports an exact location rather than a zone. It runs a test on command from the panel or from a magnet held to the housing.
- Thermal element is fixed temperature at 135 °F; the Product Line entry for this model names no other thermal function
- Sensitivity 0.5 to 4.0 %/ft, factory preset at 1.5% nominal
- 15 to 32 VDC peak; standby 200 µA at 24 VDC, 4.5 mA maximum
- Operating temperature 32 to 100 °F, narrower than the plain SD365 at 32 to 122 °F
- 2.0" high, the base setting the diameter: 6.1" on a B300-6, 4" on a B501
- Designed to meet UL 268 7th Edition; UL/ULC S1059, FM, CSFM 7272-0075:0502
SD365 is the same detector without the thermal element, and Fire-Lite lists the series as a direct replacement for the SD355. SD365T-IV is not a colour change: that suffix means CLIP and LiteSpeed, where this part is LiteSpeed only. SD365TA is the ULC version.
FAQ
What is the difference between the SD365T and the SD365T-IV?
The white SD365T runs the LiteSpeed protocol only. The ivory SD365T-IV supports both CLIP and LiteSpeed.
What does the thermal element do?
The SD365T adds a built-in 135°F (57°C) fixed-temperature thermal device to the photoelectric smoke chamber.
Is a base included?
The detector plugs into a separate base such as the B300-6 (6.1 in. diameter installed) or B501 (4 in.).
What is the operating temperature range?
32°F to 100°F, narrower than the SD365 photo-only detector at 32°F to 122°F.