ES-200X — intelligent addressable fire alarm control panel with one signaling line circuit, 198-point capacity and a pre-installed IPOTS-COM dual-technology (IP and POTS) central station communicator.
The ES-200X is a direct replacement for the MS-9200UDLS and programs just like Fire•Lite’s other addressable products, yet fits into applications previously served only by conventional panels. Its single SLC (DCL) loop carries up to 198 addressable devices — 99 detectors and 99 modules — meets NFPA Class B and Class A requirements, and runs up to 10,000 ft. (3,000 m) in LiteSpeed mode over twisted, unshielded wire. Four independently programmable NAC output circuits can each be configured Class A or Class B, with selectable strobe synchronization per NAC for System Sensor, Wheelock and Gentex appliances. The panel supports automated activation of the ECC-50/100 Emergency Command Center and the ECC-FFT firefighter telephone option, and is certified for seismic applications when used with the appropriate seismic mounting kit. The ES-200X ships as the main circuit board with display, pre-installed communicator, chassis with transformer, backbox with door, and a plastic bag containing screws, cables and key.
Specifications
| Intelligent signaling line circuits |
1; meets NFPA Class B and Class A requirements |
| Addressable device capacity |
198 (99 addressable detectors and 99 modules) |
| Programmable software zones |
99 |
| Annunciators |
16 (up to 8 per ANN-BUS) |
| SLC protocol |
LiteSpeed and CLIP |
| SLC wire run |
Up to 10,000 ft. (3,000 m) in LiteSpeed mode, twisted unshielded wire |
| Notification appliance circuits |
Terminal block provides connections for four NACs, Class B or Class A; special application power; power-limited, supervised |
| Maximum signaling current per NAC |
2.5 A special application; 250 mA regulated |
| Total 24 VDC system power |
2.7 A maximum, shared between all NAC circuits and the ANN-BUS |
| NAC end-of-line resistor |
4.7k ohm, ½ watt (P/N 71252 UL listed) for Class B NAC; system capable of 1.9k–22k ohm ELR range |
| Relays |
Two programmable Form-C relays and one fixed trouble relay; 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive); non-power-limited, non-supervised |
| AC power |
120 or 240 VAC, 50/60 Hz, 3.25 A, auto-sensing (no switch required); minimum 14 AWG (2.00 mm²) with 600 V insulation; non-power-limited, supervised |
| Battery |
Two 12 V 18 AH lead-acid; charger capacity 7–18 AH; cabinet holds a maximum of two 18 AH batteries |
| Display |
Integral 80-character LCD with backlighting |
| History file |
1,000 events |
| Backbox |
19.00" (48.26 cm) H × 16.65" (42.29 cm) W × 5.25" (13.34 cm) D |
| Door |
19.26" (48.92 cm) H × 16.82" (42.73 cm) W × 0.72" (1.82 cm) D |
| Shipping weight |
26.9 lbs. (12.20 kg) |
| Operating environment |
0–49°C / 32–120°F, relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F) |
| Standards |
Listed to UL Standard 864, 10th edition |
| Seismic |
IBC 2021, IBC 2018, IBC 2015, IBC 2012, IBC 2009; CBC 2019 |
| Agency listings (ES-200X) |
UL: S624; FM approved; CSFM 7165-0075:0500; FDNY COA #2023-TMCOAP-001919-RENL |
Installation notes
-
Power budget: 2.5 A is the per-circuit maximum. Maximum or total 24 VDC system power shared between all NAC circuits and the ANN-BUS is 2.7 A — four circuits do not give you four times 2.5 A. Add the PWRMOD24 power expander module to increase alarm power output to 6 amps.
-
Dress panel: the ES-200X carton does not list a dress panel (the ES-200XC, ES-200XI and ES-200XP do). Order DP-ES-R separately; TR-CE is the trim ring for semi-flush mounting.
-
Batteries: the cabinet holds a maximum of two 18 AH batteries and the onboard charger covers 7–18 AH. Batteries larger than 18 AH require a CHG-75 or CHG-120F and an external BB-26 or BB-55F enclosure.
-
Seismic installations: use SEISKIT-COMMENC, the seismic kit for the ES-200X Series backbox, which includes a battery bracket for two 7, 12 or 18 AH batteries.
-
Legacy devices: 300 Series devices such as CP300/CP350, SD300(T)/SD350(T), M300, M301, M302, C304 and BG-10LX are not compatible with LiteSpeed polling; if any are on the SLC, polling must be set to standard CLIP protocol.
-
Programming: databases upload and download through the panel USB port, or over ethernet using the IPOTS-COM. Offline programming with FS-Tools requires an ethernet connection.
Related models
-
ES-200XC — same panel and pre-installed IPOTS-COM, with a dress panel included in the carton.
-
ES-200XI — no communicator fitted; dress panel included.
-
ES-200XP — integrated CLSS Pathway Pro dual-SIM (AT&T/Verizon) 5G LTE-M communicator in place of the IPOTS-COM; adds ETL 5017286 and CSFM 7165-0075:0511.
-
MS-9200UDLS — the legacy panel the ES-200X Series directly replaces.
Specifications taken from the Fire•Lite Alarms data sheet "ES-200X Series Intelligent Addressable Fire Alarm Control Panels," document DF-60957:F (5/28/2025). Manufacturer specifications are subject to change without notice.