Fire-Lite MS-9200UDLS (also written MS9200UDLS) is a 198-point intelligent addressable fire alarm control panel with one SLC loop, an 80-character LCD and an on-board digital alarm communicator/transmitter (DACT).
The single signaling line circuit supports up to 198 addressable devices, 99 detectors and 99 monitor, control or relay modules. In LiteSpeed mode the loop can run up to 10,000 ft. (3,000 m). The panel has four Style Y (Class B) notification circuits, which convert to Style Z (Class A) with the optional ZNAC-92 module, and complies with NFPA 72 for local, auxiliary, remote station, proprietary and central station applications.
Specifications
| SLC capacity |
198 addressable devices (99 detectors and 99 modules) |
| Notification circuits |
Four Style Y (Class B); Style Z (Class A) with optional ZNAC-92 |
| Current per NAC |
2.5 A maximum |
| Total 24 VDC output |
3.0 A shared by all NACs and auxiliary outputs; 6.0 A with optional XRM-24B |
| Relays |
Two programmable and one fixed trouble, Form-C; 2.0 A @ 30 VDC resistive |
| AC power |
120 VAC, 60 Hz, 3.0 A (the MS-9200UDLSE is 240 VAC, 50 Hz, 1.5 A) |
| Batteries |
Charger for 7 to 18 AH; cabinet holds two 18 AH batteries |
| Communicator |
On-board DACT |
| Standards |
UL 864 (9th edition); UL S624; FM approved; CSFM 7165-0075:0208; MEA 120-06-E |
Replacement
The MS-9200UDLS is replaced by the Fire-Lite ES-200X, which keeps the same 198-point, one-loop layout. Use the ES-200X for new installations and the MS-9200UDLS to match existing systems.
Compatibility
- Larger batteries need an external charger such as the CHG-75 or CHG-120F and a separate cabinet such as the BB-26.
- Supported accessories include the ANN-BUS annunciators, the ZNAC-92 Class A converter and the XRM-24B transformer module.
- Compatible duct detector housings include the DNRW and the D355PL.
Specifications taken from the Honeywell Fire-Lite data sheet "MS-9200UDLS(E)," document DF-60601 Rev 3. Manufacturer specifications are subject to change without notice.