Fire-Lite D355PL — InnovairFlex intelligent non-relay photoelectric low-flow duct smoke detector housing, supplied with the SD355R remote-test-capable sensor head.
The pivoting housing fits either a square or a rectangular footprint and mounts to round or rectangular duct. It draws communication line power only, and a cover tamper feature reports a removed or badly seated cover as a trouble at the panel.
- Air velocity 100 to 4,000 ft/min (0.5 to 20.32 m/s)
- Operating temperature -4°F to 158°F (-20°C to 70°C); humidity 0 to 95 percent non-condensing
- Rectangular footprint 14.38 × 5 × 2.5 in.; square 7.75 × 9 × 2.5 in.
- Weight 1.6 lb (0.73 kg), with a 3/4 in. conduit knockout
- UL and ULC S1059, CSFM 3240-0075:0221, FM approved
DNRW is the NEMA-4 watertight version of the same housing and ships without a head. D365PL is the later housing, carrying the SD365R(A)-IV head that Fire-Lite lists as replacing the SD355R supplied here. The CRF-300 relay module, DST sampling tubes and the RTS151 remote test station are ordered separately.
Documents
FAQ
Is the sensor head included?
Yes. The D355PL ships with the SD355R remote-test-capable sensor head factory installed. The sampling tube is not included and must be ordered to suit the duct width.
What replaces the D355PL?
The D365PL duct smoke detector is the replacement for the D355PL.
Does it need a separate 24 VDC supply?
No. The D355PL requires communication line power only. Units with date code 0013 or higher also do not need external 24 VDC for remote test when used with a remote-test-capable detector.
Can it control fans or dampers?
Yes, with the CRF-300 addressable relay module, sold separately, which mounts inside the housing for applications requiring a Form-C relay.