VESDA VSP-006 — VLP detector chassis assembly complete with the air inlet pipe manifold, the factory-calibrated service part at the heart of a VESDA VLP aspirating smoke detector.
The chassis carries the laser detection chamber, the head processor card and the flow sensors, factory calibrated as a matched set that Xtralis warns must never be separated or mixed with parts from another VLP. Replacing it means isolating the zone, saving the node configuration in Xtralis VSC, unplugging the termination, flow sensor and scanner leads, then restoring that configuration once the new chassis is in.
- Listed as VESDA VLP Detector Chassis assembly complete with manifold
- Detection chamber, head processor card and flow sensors in one calibrated set
- Suggested stock: one spare per 50 detectors, or per 20 in mission critical use
- Xtralis lists VSP-006 as a discontinued material with no alternative
Budget for the rest: aspirator (VSP-015), filter cartridge (VSP-005), 7-relay termination card (VSP-014), cover assembly (VSP-013), display (VSP-002) and LCD programmer (VSP-001) are separate VESDA part numbers.