Silent Knight SK-MONITOR-2 — addressable dual input monitor module.
The SK-MONITOR-2 monitors two separate Class B initiating circuits from a single module and single mounting location, which is why it is commonly specified for sprinkler risers: one module covers both the waterflow switch and the tamper switch instead of two.
It interfaces contact devices generally — pull stations, waterflow and tamper switches — and can also monitor conventional four-wire smoke detectors for both alarm and trouble conditions. Addressing is set with rotary address switches on the module, and the panel-controlled status LED flashes green in normal condition and holds solid red in alarm, so the state of the circuit is readable without a meter.
Operating voltage is 15 to 32 VDC, with maximum standby and alarm current of 750 µA at 24 VDC using a 47K end-of-line resistor. It uses the Silent Knight SLC protocol and mounts in a 4-inch square electrical box of at least 2-1/8 in. depth.
Documents
FAQ
Which panels is the SK-MONITOR-2 compatible with?
Silent Knight 6820, 6820EVS, 6808, 6700, 5700, 5808, 5820XL and 5820XL-EVS fire alarm control panels.
What box does it mount in?
A 4 in. square electrical box at least 2-1/8 in. deep. The SMB500 surface mount box is available as an accessory.
Can it monitor smoke detectors?
Yes. Besides contact devices such as waterflow switches and pull stations, it can monitor conventional four-wire smoke detectors for alarm and trouble.
What end-of-line resistor does it use?
A 47K end-of-line resistor on each Class B circuit.