Siemens FC922-UE — Cerberus PRO electronics package for a 252-point FC922 fire alarm control panel, part number S54400-C16-A1.
Siemens sells the FC922 as an electronics package plus an enclosure ordered separately, and this is the electronics half: three boards that make a working 252-point panel once mounted in a two-height-unit enclosure.
- One FP2011-U1 170 W power supply, one FCI2016-U1 252-point periphery board, one FCM2019-U3 operating interface unit with 24 zone LEDs
- FP2011-U1 gives regulated 24 VDC nominal rated 6.5 A, with a 4.0 A slow-blow primary fuse
- C-NET loop for up to 252 addresses, one to four Class B or one to two Class A
- One Class A or two Class B notification circuits, four Form C relays, 24 VDC auxiliary at 1.5 A
- Backlit 2 × 4-3/4 in. LCD, four-way navigation, 10,000-event history log
- UL 864 10th Edition and ULC-S527 listed; FM, CSFM and FDNY approved
No enclosure is supplied. A complete two-height-unit housing takes an FHB2002-U1 back box, one or two inner doors, an FHD2002 or FHD2003 outer door and its FHD2006-U1 windows; trim kit, battery bracket and DIN rail kit are optional. FC922-US is this package with the plain FCM2018-U3 unit.