Notifier RP-2002E — six-zone agent release control panel, the 220/240 VAC version of the RP-2002.
The panel drives agent releasing for single and dual hazard applications and also serves as the building fire alarm control panel. Six Class B initiating circuits take smoke detectors, pull stations and waterflow switches, and each of the four outputs is programmable as a notification appliance circuit or a releasing circuit.
- Input 240 VAC, 50/60 Hz, 2.085 A; RP-2002 is 120 VAC, 3.66 A
- 7.0 A total 24 VDC output
- Six Style B initiating circuits, 4.7 kΩ end-of-line, Style D with the N-CAC-5X
- Cross-zone double-interlock, abort, adjustable discharge timers
- UL 864 9th edition, file S635, FM approved; NFPA 12, 12A, 12B, 2001
- Charger takes 7 to 26 Ah batteries; two 18 Ah cells fit the cabinet
Notifier ships the panel with its backbox, power supply and manuals; batteries and the DP-51050 dress panel are separate. The IBC seismic compliance claimed in the features is realised only with the SEISKIT-COMMENC kit, which Notifier marks as required and does not supply. The RP-2002 is the same panel on 120 VAC.