Notifier NP-200R — white low-profile intelligent photoelectric smoke sensor, remote test capable, for DNR and DNRW duct smoke detector housings.
This is a plug-in sensor head, not a finished detector. It uses a separate base for its wiring and, in duct service, drops into a DNR or DNRW housing that Notifier sells without a head. The R marks remote test, run from the panel instead of reaching the duct.
- FlashScan only; Notifier states the series is exclusively for its FireWarden Series panels
- Voltage range 15 to 32 volts DC peak from the signaling line circuit
- Standby 200 µA and maximum 4.5 mA, both at 24 VDC
- Sensitivity 0.5 to 4.0 percent per foot obscuration, UL applications
- Operating temperature -4 to 158 °F installed in a DNR or DNRW housing
- Rated velocity range 0 to 4000 ft/min
- Meets UL 268 7th Edition; UL and ULC certification S1115
The ivory NP-200R-IV is the same head carrying CLIP as well as FlashScan, so the two are not interchangeable where CLIP is required. The plain NP-200 has no remote test and the NP-200T adds a thermal element. A base such as the B300-6 or B501 is a separate number.
Documents
FAQ
Is the NP-200R a complete duct detector?
No. It is a plug-in sensor head that drops into a DNR or DNRW duct housing, or mounts on a separate base such as the B300-6 or B501.
Which panels support it?
It is FlashScan only, and Notifier states the series is exclusively for its FireWarden Series panels.
What does the R mean?
R marks remote test capability, so the sensor can be tested from the panel instead of at the duct.
Is there a CLIP version?
The ivory NP-200R-IV supports CLIP as well as FlashScan.