Notifier NFN-GW-EM-3 is the embedded NOTI•FIRE•NET (NFN) gateway for the ONYXWorks fire monitoring workstation. It gives the workstation full monitoring and control of an NFN network, plus panel programming and network diagnostics.
As a standalone embedded gateway with IP capability, it lets ONYX Series users monitor several sites over an Ethernet network without remote workstations. It works with NFN version 5.0 and higher and with high-speed NFN, serving ONYXWorks, ONYX FirstVision, ONYX Series panels, DVC-EM, the BACnet gateway and the NCA-2.
Specifications
| Power input |
24 VDC |
| Input current |
450 mA at 24 VDC (without NCM) |
| Operating temperature |
32 to 120°F (0 to 49°C) |
| Network |
NFN v5.0 or later, or high-speed NFN |
| Direct panel connection |
NFS2-640, NFS-320, NFS2-3030 |
| Standards |
UL 864, UL 2017, UL 2610, ULC S559-04, ULC S527-99 |
| Approvals |
UL/ULC S5697, FM, CSFM 7300-1525:0103, FDNY COA 6306, 6287 |
| Included |
PC board, NUP-to-NUP cable (75577), USB cable (75665), NFN configuration |
Features
- Monitors alarm, prealarm, trouble and disabled events from ONYX panels
- Adds acknowledge, silence, reset, enable/disable and activate/deactivate control to the workstation
- Supports panel program upload, download and changes
- ONYXWorks supports up to 200 gateways; several workstations can use one gateway at a time
- Supervised IP connections and gateway redundancy
Installation notes
- NFN connection requires an NCM; high-speed NFN requires an HS-NCM
- Also required: a Windows 10 PC, RJ45 Ethernet cable, ONYXWorks or FirstVision, and VeriFire Tools
- A certified Ethernet (TCP/IP) switch is required between a shared IP network and the ONYXWorks equipment
Related models
NFN-GW-PC-F and NFN-GW-PC-W are the PC-based NFN gateways.