Notifier FPTI-951-IV — plug-in addressable multi-criteria detector combining photoelectric, thermal and infrared sensing in one ivory head.
The FPTI-951 Series replaces the FAPT-851 Series. The photoelectric chamber sees smoke particles, the thermal element responds to rate-of-rise and a 135 °F fixed threshold, and infrared reads light patterns as a third input, so the algorithm can reject nuisance sources such as theatre smoke. It meets both smoke and heat certification requirements and reports the two alarms distinctly.
- The -IV suffix denotes protocol, not colour: this model runs FlashScan or CLIP, where the white FPTI-951 is FlashScan only
- UL 268 7th Edition and UL 521 certified; FM Approved; UL/ULC S1111
- 15 to 32 VDC; 200 µA standby at 24 VDC, 2 mA alarm, 4.5 mA maximum
- 4.1 in. diameter on a B501 base or 6.2 in. on a B300-6 base; 2.0 in. high
- 32 °F to 100 °F, 15% to 90% humidity, air velocity to 300 ft. per minute
The head ships without a base; order B501-IV, B300-6-IV, B224BI-IV isolator, B224RB-IV relay or B200S-IV sounder base separately. Do not confuse it with the white FPTI-951, FlashScan only, or the ULC FPTI-951A and FPTI-951A-IV.
Documents
FAQ
Is a base included with the FPTI-951-IV?
No. The head ships without a base; Notifier lists the B501-IV and B300-6-IV mounting bases, the B224BI-IV isolator base, the B224RB-IV relay base and the B200S-IV sounder base for the ivory version.
What does the -IV suffix mean?
On the FPTI-951 Series, -IV models are ivory and support both FlashScan and CLIP protocols. The white FPTI-951 supports FlashScan only.
What should replace a discontinued FPTI-951-IV?
Our catalog points to the FPTI-951. Per the data sheet it is the white, FlashScan-only version, so confirm the loop runs FlashScan before using it on a CLIP system.
What are the heat and environmental limits?
The thermal sensor uses a 135 °F fixed threshold plus rate-of-rise. The detector is rated for 32 °F to 100 °F, 15% to 90% RH and air velocity up to 300 ft/min.