Notifier 50160636-001 — CLSS Gateway Kit, containing a 30 in. NUP cable and a NOTIFIER lock and key set.
Read the contents before ordering, because no gateway comes with it. Honeywell lists the CLSS Gateway separately as HON-CGW-MBB, with CGW-MB the bare board and CGW-BB the enclosure. This kit connects and secures one of those.
- Contents as the manufacturer states them: one 30 in. NUP cable and one NOTIFIER lock and key set
- The cable joins the NUP and RS-232 port on the gateway board to the Network Service Connection on a Notifier panel
- That port can also feed the gateway: switch S7 at NUP IN draws 24 V through it, while NUP OUT takes power from the separate supply port
- Where 30 in. will not reach, 32351718-001 is the 10 ft NUP serial RS-232 cable kit
Two Honeywell documents list this part in the same words, in the CLSS Gateway datasheet ordering block and in the Installation and Users Manual parts table, and neither names a board, enclosure or bracket in its contents. Buyers wanting the gateway itself want HON-CGW-MBB.