Napco FL-32FACP-LTEVS is a FireLink conventional 8 to 32 zone fire alarm control panel with a built-in sole-path LTE cellular communicator (Verizon) and an integral menu-driven LCD annunciator.
The panel ships preprogrammed for 8 conventional zones, with zone 1 set for waterflow and zone 2 for supervisory (tamper). It can be expanded to 32 points with conventional or addressable devices. Programming is done from the cloud, with Quickloader software, or by using the default program. The onboard StarLink Fire communicator reports to any central station and is described by Napco as replacing two POTS lines. This model is discontinued; the current replacement is the FLX2-32.
Specifications
| Zones |
8 conventional, expandable to 32 points |
| Addressable |
1 SLC loop, up to 32 points |
| NACs |
2 programmable, 2 A max total at 24 V |
| Power supply |
4 A at 24 V |
| Auxiliary power |
12 V regulated, 2 A |
| Communicator |
Sole-path LTE cellular (Verizon) |
| Annunciators |
Up to 6 additional GEMC-FK1 or FL-FK1 |
| Enclosure |
Red, locking; 16 x 14.25 x 5.2 in without cover |
| Battery capacity |
Up to 16 Ah at 24 V in cabinet |
| Operating environment |
32 to 120°F, up to 93% RH non-condensing |
| Agency |
UL 864 10th Ed., UL 1635, NFPA 72, CSFM, FDNY COA |
Features
- Built-in sync for System Sensor and Wheelock notification appliances on each NAC
- One NAC can be set for 12 V for retrofit of legacy appliances
- Two onboard serial ports, one for high-speed local downloading
- Surface or flush mounting; flush mounting requires external antennas
- 36-month Napco warranty
Related models
- FLX2-32: replacement 32-zone FireLink panel
- FLX2-255: FireLink 255-point addressable panel
Documents
FAQ
What replaces the FL-32FACP-LTEVS?
This model is discontinued. The replacement is the Napco FLX2-32 FireLink 32-zone panel with dual SIM cellular communicator.
Which cellular network does it use?
The FL-32FACP-LTEVS has a built-in sole-path StarLink Fire LTE communicator on Verizon. Napco states it replaces two POTS lines and reports to any central station.
Can it use addressable devices?
Yes. It starts with 8 preprogrammed conventional zones and expands to 32 points, including one 32-point addressable SLC loop for analog smoke and heat detectors, duct detectors, pull stations, zone modules and isolators.
What battery capacity fits in the cabinet?
The locking enclosure houses up to 16 Ah at 24 V of battery backup.