9-30783-KID-ULF is the Kidde ModuLaser detector module, the self-contained aspirating unit of the ModuLaser modular aspirating smoke detection system. Each detector module draws air from its own sampling pipe zone, analyzes it with laser light scattering and ClassiFire artificial intelligence, and drives local relays for pre-alarm, alarm and fault. It reports to a separately ordered display module over RS-485 (SenseNET+); a Minimum or Standard display module supports up to 8 detector modules in a cluster.
Specifications
| Operating voltage |
24 VDC nominal (18.0 to 30.0 V) |
| Current at 24 VDC |
218 mA (fan speed 1); 330 mA (fan speed 6, default); 762 mA (fan speed 16) |
| Detection principle |
Laser light scattering mass detection and particle evaluation |
| Particle sensitivity range |
0.003 to 10 microns |
| Sensitivity range |
0.00914 to 7.62 %obs/ft (0.03 to 25 %obs/m) |
| Alarm levels |
4 (Aux, Pre-alarm, Alarm, Alarm 2) |
| Sampling pipe |
Up to 820 ft (250 m) combined; up to 50 sampling holes (design with PipeCAD) |
| Inlet / exhaust |
1.06 or 0.98 in. (27 or 25 mm) OD; top or bottom; one inlet per module |
| Inputs |
2 supervised, 15 kΩ 5% 1/4 W termination, programmable |
| Outputs |
3 voltage-free relays, 2 A at 30 VDC, NO/NC/C, programmable |
| Event log |
20,000 events per module |
| Connectivity |
RS-485 (SenseNET+), USB Type A and Type B, Ethernet |
| Dimensions (W x D x H) |
4.35 x 5.25 x 11.8 in. (110.5 x 133.5 x 300 mm) |
| Weight |
3.46 lb (1.57 kg) |
| Mounting |
19 in. rack, DIN rail or surface; vertical orientation |
| Operating temperature |
0 to 38 °C (UL/ULC); 0 to 49 °C (FM) |
| Humidity / rating |
0 to 90% noncondensing; indoor, IP40 |
| Certification |
FM, UL 268 7th edition, UL 268A, CSFM, ULC S529 (4th edition) |
Compatibility and installation notes
- Requires a display module, ordered separately: 9-30780-KID-ULF, 9-30781-KID-ULF (Standard) or 9-30782-KID-ULF (Command). A Command display module cannot replace a Minimum or Standard module within a cluster.
- Listed for open area protection and special application under UL 268 and for duct detection under UL 268A, with duct airflow up to 4,000 ft/min.
- Spare parts listed: 9-30791-2 detector cover, 9-30797 accessory kit, 9-30794 grommets, 9-30795 and 9-30796 pipe adapters, 9-30798-2 wiring housing, 9-30699N-P filter pack (6).
Documents
Specifications from Kidde data sheet K85001-1040, ModuLaser Detector Module, Issue 1.1 (12-16-25). Manufacturer specifications are subject to change.