Fire-Lite IPDACT-2 — FireWatch IP alarm communicator that moves a panel's Contact ID reporting onto Ethernet instead of phone lines.
It wires to the primary and secondary telco ports of a DACT-equipped Fire-Lite panel and holds supervised line voltage on both, so the panel dials as it always did and needs no reprogramming. It catches the off-hook, packetizes the Contact ID into encrypted UDP and sends it to a Teldat VisorALARM PLUS receiver, supervised every 30 to 90 seconds instead of daily.
- Panels: MS-5UD, MS-10UD, MS-5024UD, MS-5210UD, MS-9050UD, MS-9200UD, MS-9200UDLS, MS-9600 with DACT-UD, MS-9600LS / MS-9600UDLS with DACT-UD2
- Two supervised inputs, two outputs; 10/100 Ethernet, DHCP or static IP
- 24 VDC nonresettable, filtered, regulated: 93 mA standby, 136 mA alarm
- UL 864 Ninth Edition certified (UL S2424, CSFM 7300-0075:223)
It reports only to a Teldat VisorALARM PLUS IP receiver, and the central station issues the account ID, receiver addresses and UDP port. The plain IPDACT-2 has no upload/download modem — that is the IPDACT-2UD.