Flush Mount Sampling Point Head Only Flush Mount Sampling Point Head Only for 6mm, 8mm, 10mm Capillary tubing GREY
Grey flush-mount sampling point for Xtralis / VESDA aspirating smoke detection capillary sampling, offered as an alternative to the conical sampling point. It installs from the room side of the ceiling using wing-locks and accepts 6 mm, 8 mm, 10 mm or 1/2 in capillary tube by push fit. A snap-fit fascia hides the sampling hole, which starts as a 2 mm pilot hole and can be drilled out to suit the design.
Key Features
- Installs from below the ceiling with a wing-lock clamp; wing-lock height adjusts to panel thickness
- Push-fit connection for 6 mm, 8 mm, 10 mm and 1/2 in capillary tube
- 2 mm (5/64 in) pilot sampling hole, can be drilled out up to 5 mm (13/64 in) per ASPIRE design
- Tapered sampling hole helps resist clogging
- Snap-fit fascia conceals the hole and removes for cleaning
- Carries the text 'XTRALIS FIRE DETECTION SYSTEM - DO NOT PAINT'
- RoHS / REACH compliant
- Optional VSP-878 push-in connect adaptor kit for 1/2 in tubing
Specifications
| Dimensions |
92 x 54 mm (3.7 x 2.13 in) |
| Capillary tube sizes |
6 mm, 8 mm, 10 mm, 1/2 in |
| Sampling hole |
2 mm pilot, up to 5 mm |
| Ceiling cutout |
32 mm to 35 mm |
| Colour |
Grey |
Compatible With
- All Xtralis aspirating smoke detectors (VESDA, VESDA-E)
- VSP-878 push-in connect adaptor kit