VESDA-E VEU-A00-UL — the UL 268 7th Edition build of the VEU, the highest-sensitivity aspirating smoke detector of the VESDA-E range from Xtralis, in an aluminum enclosure with LED indication.
An aspirating detector draws air continuously from a sampling pipe network back to a chamber rather than waiting for smoke to reach a detector. In the VEU that chamber is Flair, imaging particles with a CMOS imager and photodiodes.
- Sensitivity 0.0003% to 6.575% obscuration per foot; four alarm levels
- 18 to 30 VDC; 0.29 A quiescent to 0.64 A in alarm at aspirator setting 10
- Coverage to 69,965 sq. ft., 96 holes, 2,001 ft of pipe
- Inlet and exhaust 3/4 in. IPS; seven relays, 2 A at 30 VDC
- 13.8 × 8.9 × 5.3 in., 11.7 lb, IP40; 32 to 100 °F
- VESDAnet, Ethernet, USB; 20,000-event log
- UL 268 7th Edition, ULC, CSFM, FM, FDA, FCC, RCM
A00 is the Xtralis code for the LED front cover; VEU-A10-UL is the same detector with a 3.5 in. display instead. Do not carry figures over from the international VEU-A00, which differs in specification, not only listing: it allows 2,625 ft of pipe and 100 holes.
Documents
FAQ
What does A00 mean in VEU-A00-UL?
A00 is the LED front cover. The VEU-A10-UL is the same detector with a 3.5 in. display.
How large a pipe network does it support?
Up to 2,001 ft of pipe and 96 sampling holes, covering up to 69,965 sq. ft.
What power does it need?
18 to 30 VDC, drawing 0.29 A quiescent to 0.64 A in alarm at aspirator setting 10.
Can figures from the international VEU-A00 be used?
No. The international VEU-A00 differs in specification, allowing 2,625 ft of pipe and 100 holes.