VESDA OSE-SPW — standard power wired emitter for the Xtralis OSID-DE open-area smoke imaging detection system, powered from 24 VDC.
OSID-DE pairs emitters with an imager: the emitter sends dual wavelength infrared and ultraviolet beams to the imager's CMOS sensor. The system tolerates vibration and structural movement and tells smoke from environmental conditions better than a traditional beam detector. One OSI-90 imager can work with up to seven emitters. The wired emitter suits sites where 24 VDC is close by; battery-powered emitters cut wiring where it is not.
Specifications
| Model |
OSE-SPW |
| Supply voltage |
20 to 30 VDC (24 VDC nominal) |
| Current |
350 µA at 24 VDC |
| Range with OSI-10 |
30 to 150 m (98 to 492 ft) |
| Range with OSI-90 |
6 to 34 m (20 to 111 ft) |
| Operating temperature |
14 °F to 131 °F; UL certified 32 °F to 100 °F |
| Humidity |
10% to 95% RH, non-condensing |
| Dimensions |
8.2 in. W x 5.4 in. H x 3.8 in. D |
| Weight |
535 g |
| Adjustment |
±60° horizontal, ±15° vertical |
Installation notes
- Alignment uses the ball and socket mount with the OSP-002 laser alignment tool.
- OSID-EHE environmental housing (IP66, NEMA 4-4X) protects emitters from dust and water.
- OSID-WG wire guard protects against vandalism and accidental damage.
- OSE-ACF anti-condensation film is available for the emitter lens.
Related models
- OSE-SP-01 is the battery-powered standard emitter.
- OSE-HPW is the high power wired emitter, which doubles the OSI-90 range.
- OSI-10 (one emitter, long range) and OSI-90 (up to seven emitters) are the imagers.
Documents
FAQ
Which imagers does it work with?
The OSI-10 imager (8° field of view, 30 to 150 m, one emitter) and the OSI-90 imager (80° field of view, 6 to 34 m, up to seven emitters).
What power does the emitter need?
20 to 30 VDC, 24 VDC nominal, drawing 350 µA. The battery-powered alternative is the OSE-SP-01.
How precise does alignment need to be?
The maximum misalignment angle is ±2°. The OSP-002 laser alignment tool aligns and locks the emitter.
Can it be used in dusty or wet areas?
Use the OSID-EHE emitter environmental housing, rated IP66 and NEMA 4-4X.