Thermotech 302-AW-135 — all-weather rate-anticipation spot heat detector, 135°F (57°C), for vertical mounting.
The 302 Series actuates whenever the ambient temperature reaches the alarm setting, regardless of the rate of rise. Under rapid heat rise, the rate anticipation feature lets the detector respond one to three degrees ahead of the setting, while it ignores momentary fluctuations below the alarm level. When the temperature drops back below the setting, the detector resets itself. The sensing shell is high-expansion anodized aluminum, and the fine silver contacts are hermetically sealed.
Specifications
| Model |
302-AW-135 |
| Alarm temperature |
135°F (57°C) |
| Operation |
Rate anticipation, self-restoring |
| Contacts |
Normally open |
| Electrical rating |
6–28 VDC, 1 A |
| UL spacing |
50 x 50 ft |
| FM spacing |
20 x 20 ft (rate of rise); 10 x 10 ft fixed temperature only |
| Maximum ambient |
100°F (38°C) |
| Minimum ambient |
-40°F (-40°C) |
| Construction |
Moisture and dust proof, all-weather leads |
Installation notes
- No special back box is required when the all-weather leads are properly spliced to THW or equivalent wire
- The AP-P adapter plate is required to mount the detector to a 4 in. outlet box
- Detectors must not be painted; refer to NFPA 72 for spacing and application requirements
Related models
- 302-AW-194: same all-weather detector, 194°F
- 302-ET-135: all-weather with 1/2 in. conduit thread bushing
- 302-135: interior model with terminals
- 302-EPM-135: explosion-proof model
Documents
FAQ
Does the 302-AW-135 need to be reset after an alarm?
No. It resets itself automatically when the temperature drops back below the alarm setting.
Does it need a special back box outdoors?
No. It is moisture and dust proof and needs no special back box when its all-weather leads are properly spliced to THW or equivalent wire. Mounting to a 4 in. outlet box requires the AP-P adapter plate.
What spacing does it have?
UL spacing is 50 x 50 ft. FM spacing is 20 x 20 ft for rate of rise, or 10 x 10 ft as fixed temperature only.
What is the electrical rating?
The normally open contacts are rated 6 to 28 VDC, 1 A.