Thermocable F3050 — PVC coated analogue linear heat detection sensor cable for the ProReact EN Analogue system.
Linear heat detection covers runs where a fire can start anywhere and point detectors cannot see it. Polymers inside the cable drop in resistance as temperature rises; the ProReact EN Analogue Composite Control Unit measures that resistance and the average ambient along the run, giving pre-alarm and alarm from one cable.
- Four-core twisted with 100% foil shield; red PVC coat, 4.83 mm (0.190 in) diameter
- Minimum bend radius 60 mm (2.36 in); minimum ambient -40 °C
- Zone length 30 to 50 m minimum by setting, 500 m maximum
- Alarm temperature is set at the control unit, not by the cable: Class A1I/A2I, Class BI, or 54 to 100 °C
- VdS EN54-22 approved, certificate G220006; UL 521 certified, file S8976
F3051 is the same cable in a nylon jacket, UV stable for sunlight; F3052 adds a steel braid but is VdS approved only, not UL 521 certified. Use only with the A1389 control unit and A1470 end-of-line unit. F3050 covers 100 m, 250 m and 500 m reels under one part number, so confirm reel length.
Documents
FAQ
Where is the alarm temperature set?
At the ProReact EN Analogue Composite Control Unit, not by the cable. Settings include Class A1I/A2I (66°C nominal), Class BI (80°C) and fixed alarms from 54 to 100°C.
Does it respond to fast temperature rises?
Yes. With the class settings, the control unit also triggers an alarm if about 2% of the sensor cable is heated at more than 15°C per minute for longer than 3 minutes.
How does it connect to a fire alarm panel?
Through the control unit, either to an addressable loop using a zone or switch monitor or I/O module, or directly to the initiating zone of a conventional fire alarm control panel.