Telguard TG-7FE-V — Verizon version of the TG-7FE dual path commercial fire alarm communicator, listed for use in the United States.
It presents dial tone to a fire alarm control panel, takes the account number and zone data by dialer capture as a central station receiver would, and delivers it to the Telguard Communication Center over cellular or a wired LAN. It runs dual path with either route primary, or sole path cellular with link supervision.
- UL 864 for fire and UL 1610 for central-station burglary; the Verizon model has no ULC listing
- Verizon LTE-M radio on bands 4 and 13, 256-bit AES, with SMS as the secondary route
- Link supervision selectable at 5 or 60 minutes
- Contact ID, SIA2, Modem IIe and IIIa2, pulse formats, Sonitrol and DMP
- 110 mA idle, 260 mA transmitting on 12 VDC panel power
- Red painted metal enclosure, 11.4 in. × 7.75 in. × 3.3 in., 0 to 49 °C
TG-7FE-A is the AT&T version and the one listed to ULC S559 and ULC S304 for Canada. TG-7E-A and TG-7E-V are the same hardware without the UL 864 fire listing. A 12 VAC transformer is supplied; the standby battery is not.