Outdoor Air Sensor
Outdoor air temperature sensor with a 1000 ohm platinum RTD element, enclosed in a sealed standard aluminum box with a conduit junction. It can be converted for duct mounting by changing the position of the PVC probe.
Key Features
- Sealed standard aluminum box with conduit junction
- PVC probe can be repositioned for duct-mount use
- Compatible with TCS room controllers and other thermostats that read a remote 1000 ohm RTD
Specifications
| Sensor type |
1000 Ohm platinum RTD |
| Reference resistance |
1000 Ohm @ 32°F (0°C) |
| Temperature coefficient |
0.00385 Ohm/Ohm/°C |
| Accuracy |
+/-0.1% @ 32°F (0°C) |
| Response time (90%) |
Air @ 1 m/s: 25 s; air @ 3 m/s: 17 s |
| Operating temperature |
-50 to 375°F (-45.6 to 190.6°C) |
| Maximum current |
5 mA (1 mA recommended) |
| Compliance |
DIN IEC 751 |
| Stability |
< 0.05% drift per year |
Compatible With
- TCS Basys room controllers (e.g. UbiquiSTAT)