System Sensor DCOIL — 2-wire remote test coil, the accessory some InnovairFlex duct smoke detectors need before a remote test station can test them.
A remote test station such as the RTS151 or RTS151KEY lets a technician test a duct detector from a reachable location. On the housings below the station cannot run that test until this coil is installed, and System Sensor sells it separately.
- D2 2-wire conventional duct detector: the D2 data sheet and RTS151 manual both say using an RTS151 or RTS151KEY requires the DCOIL, sold separately
- DNR and DNRW housings with a date code of 0012 or earlier need a DCOIL and auxiliary 24 VDC for remote test
- DNR and DNRW housings dated 0013 or later need neither, when used with a remote test capable detector
- RTS151 and RTS151KEY draw 0 mA standby and 12 mA maximum in alarm at 24 VDC
- The D2 ordering row ties DCOIL to the older RTS451 and RTS451KEY, which the RTS151 replaces
Not for every duct detector: the RTS151 manual says a test coil is needed only on D2, DNR, DH400 and DH500 models, and the DH400 and DH500 take a different part, COIL. The 4-wire D4120 is not on that list.