Siemens SL2SCW-F — SL2 Series LED ceiling strobe, clear lens, white faceplate lettered FIRE, part number S54329-F198-A1.
The SL2 series carries an LED in place of the xenon flashtube, cutting strobe current at every setting while still meeting the 20 millisecond light-pulse-duration requirement of NFPA 72 2016, so SL2 appliances and existing Siemens xenon strobes may share one field of view. This model is a strobe alone and carries no horn.
- Six settings on a slide adjuster: 15, 30, 75, 110, 150 and 177 cd
- Drawing 0.022, 0.030, 0.060, 0.086, 0.125 and 0.185 A at 24 V
- Regulated range 16.0 to 33.0 V, DC or VFWR; this model is 24 V only
- Certified to UL 1638, UL 1971 and ULC-S526-16; indoor ceiling use only
- 32 °F to 122 °F (0 °C to 50 °C), 93% relative humidity maximum
- Flush mounts to a single-gang, 4 in. square or octal box
The SL2SCR-F is the same ceiling strobe with a red faceplate and the SL2HSCW-F adds a horn to the white FIRE housing. The suffix sets lettering and lens: SL2SCW-N has none, SL2SCW-A reads AGENT, and SL2SCW-ALA and SL2SCW-ALB carry amber and blue lenses rather than clear.
Documents
FAQ
Can SL2 LED strobes be mixed with existing Siemens xenon strobes?
Yes. SL2 appliances meet the 2016 NFPA 72 light pulse requirement, so existing xenon and new LED strobes can be used in the same notification zone and field of view.
Is the SL2SCW-F for outdoor use?
No. The SL2 series is UL and ULC certified for indoor, ceiling-mount use only.
What voltage does it need?
The SL2 strobes are for 24 V operation, 16.0 to 33.0 V DC or VFWR.
How are SL2 strobes synchronized?
With Siemens dual-sync (DSC) modules or panels using the Siemens proprietary synchronization protocol.