Simplex 4906-9160 is a ceiling-mount TrueAlert non-addressable multi-candela speaker/visible (S/V) appliance with a red housing and white "FIRE" lettering. It pairs a multi-tapped speaker with a synchronized xenon strobe whose intensity is selectable at 15, 30, 75 or 110 cd, so one model covers different room requirements. Installers use it where a ceiling appliance must provide both voice/tone and visible notification.
Specifications
| Strobe intensity |
15, 30, 75 or 110 cd (selectable) |
| Strobe voltage |
Regulated 24 VDC, 16 to 33 VDC |
| Max RMS strobe current |
80 / 127 / 269 / 371 mA at 15 / 30 / 75 / 110 cd |
| RMS current at 24 VDC |
50 / 83 / 155 / 211 mA |
| Flash rate |
1 Hz, up to 35 synchronized strobes per NAC |
| Speaker input |
25 VRMS or 70.7 VRMS |
| Speaker taps |
1/4 W, 1/2 W, 1 W, 2 W |
| Frequency response |
400 Hz to 4000 Hz (fire alarm) |
| Housing |
7-1/2 in. (191 mm) diameter, 1/2 in. (13 mm) deep; lens protrudes 2-5/8 in. (67 mm); 2-3/4 in. (70 mm) depth into box |
| Operating environment |
32 to 122 degrees F (0 to 50 degrees C), 10% to 93% humidity, non-condensing |
| Connections |
Terminal blocks for 18 to 12 AWG |
| Certification |
UL certified (UL 1480 speaker, UL 1971 strobe) |
Installation notes
- Strobe intensity is set with a selection plug at the back of the housing; a flag at the side of the lens shows the selected setting.
- Strobes synchronize from NACs that use the Simplex synchronization format, or from a 4905-9914 (Class B) or 4905-9922 (Class A) flash module.
- Mounts to 4 in. electrical boxes with an extension; the 2905-9946 tile bridge is the ceiling tile support.
- Speaker and strobe are wired separately, with in/out wiring on each terminal.