Simplex 4100-9600 is the MINIPLEX Basic Transponder for 4100ES systems: bay equipment with a power distribution interface (PDI) and the 4100-0620 Basic Transponder Interface Module mounted in Block A. A MINIPLEX transponder lets initiating and notification modules sit at a remote location while the host 4100ES panel controls them over a Remote Unit Interface (RUI) link, so long multiple wiring runs back to the panel are not needed.
Specifications
| Includes |
Bay assembly, PDI, 4100-0620 Basic Transponder Interface Module (Block A), interconnect harness |
| Host communications |
RUI or RUI+, Class B or Class X |
| Distance to host |
Up to 2,500 ft (762 m) |
| RUI capacity |
Up to 31 remote devices in total |
| Current |
36 mA supervisory; 36 mA alarm |
| Enclosure |
NEMA 1/IP30 box and solid door, platinum or red, ordered separately |
| Batteries |
Bottom compartment takes two batteries up to 50 Ah; a power supply with charger is required for each battery set |
Compatibility and installation notes
- Box and door are ordered separately (enclosure details in Simplex data sheet S4100-0037).
- One power distribution module per box: 4100-0634 for 120 VAC or 4100-0635 for 220/230/240 VAC.
- ES power supplies are selected separately; the ES-PS mounts in blocks G and H.
- Up to eight close-nippled cabinets can be connected at one transponder location.
Related models
- 4100-9601: Local Mode Transponder with the 4100-0625 module, which keeps default local fire alarm operation if communication with the host is lost
-
4100-0620: Basic Transponder Interface Module
-
4100-0634: 120 VAC power distribution module
-
4100-0635: 220/230/240 VAC power distribution module
-
4100-5401: ES-PS power supply with battery charger
Documents
Specifications from Simplex data sheet S4100-1035 Rev. 7, 08/2024, MINIPLEX Transponders with ES-PS Power Supplies. Manufacturer specifications are subject to change.