Simplex 4100-6052 — serial digital alarm communicating transmitter (SDACT) for 4100ES and 4100U panels.
An SDACT is how a Simplex panel talks to a central station over telephone lines. Instead of a bare contact closure, this module communicates with the panel CPU and sends specific point information — which device, which condition — so the station can dispatch accurately.
- Single 2 in slot module; up to two 4100-6052 SDACTs per 4100ES/4100U
- Dual phone line interface; two RJ31X jacks, Data Certified POTS lines
- Contact ID (preferred), 3/1, 4/2, BFSK and SIA level 1; ten events per call
- Programmable 6-hour test and power-fail report delay
- 18–32 VDC from panel; 30 mA standby, 40 mA reporting
- UL 864 certified per NFPA 72 for Central Station Service; FCC Part 68
Check the mounting first. The 4100-6052 is the slot-mounted SDACT; a 4100ES built with the EPS power supply takes the 4100-6080, which mounts to the left side of the CPU bay end support or an expansion bay. They are not substitutes.
Documents
FAQ
Which panels take the 4100-6052?
The 4100ES and 4100U. It is a single 2 inch slot module, and up to two can be used per system.
What phone lines does it need?
Two Data Certified POTS lines on RJ31X jacks. Two 14 ft SDACT cables are included with the 4100-6052.
Which reporting formats are supported?
Contact ID (preferred), 3/1 and 4/2 pulse, BFSK and SIA level 1.
Can it be used on a 4100ES with the EPS power supply?
Use the 4100-6080 for a 4100ES with EPS. It mounts to the left side of the CPU bay end support or an expansion bay.