Simplex 4100-5013 is an 8-point zone/relay module for 4100ES fire alarm control units. Each of the eight I/O points can be configured as a Class B conventional initiating zone, a relay point or a Class B security point, and two adjacent points can form a Class A zone. Installers use it to add conventional detector zones or relay outputs to a 4100ES panel.
Specifications
| Points |
8, independently configurable |
| Zone capacity |
Up to eight Class B or four Class A zones |
| Relay rating |
2 A at 30 VDC or 30 VAC, non-inductive (dry contacts) |
| Zone rating |
32 V maximum, 74 mA maximum, 3.0 mA maximum detector standby load |
| Maximum wiring impedance |
50 ohms |
| Card size |
4 in. x 5.65 in. (10.16 cm x 14.35 cm) |
| Maximum card current |
619 mA at 24 V from the panel |
| Operating temperature |
32°F to 120°F (0°C to 49°C) |
| Humidity |
Up to 93% RH at 100°F, non-condensing |
Installation notes
- Plugs into an available PDI block in the control unit bay and secures with two #6-32 screws
- Zone circuits are supervised and power limited
- Some detectors need the 4100-5130 25 V regulator module; order harness 4100-6305 for each card it powers
- Use a 3.3 kΩ, 1 W end-of-line resistor (4081-9002) for Class B zones