Simplex 4100-3109 — IDNet 2 module for Simplex 4100ES fire alarm control panels, with 250-point capacity and two short-circuit isolating output loops.
The IDNet 2 module provides a signaling line circuit for up to 250 IDNet addressable monitor and control points intermixed on the same pair of wires. Its output is electrically isolated from other system reference voltages to reduce common mode noise from adjacent wiring, and each of its two loops can be wired Class A or Class B. The module occupies one block and is the standard IDNet 2 module supplied on the EPS.
Specifications
| Model |
4100-3109 |
| Capacity |
250 addressable points per module |
| Output loops |
Two, Class A or Class B, short-circuit isolating |
| Mounting |
1 block |
| Current, no devices |
50 mA supervisory, 60 mA alarm |
| Current, 250 devices |
250 mA supervisory, 350 mA alarm |
| Wiring distance |
4000 ft (50 ohms) for 1–125 devices; 2500 ft (35 ohms) for 126–250 devices |
| Class B T-tap total |
Up to 12,500 ft; 0.60 µF |
| Wire |
Shielded or unshielded, twisted or untwisted; 18 to 12 AWG terminals |
| Compatibility |
IDNet devices and TrueAlarm sensors, including QuickConnect and QuickConnect2 |
Installation notes
- Up to two 4100-3111 IDNet loop output modules can be added to a 4100-3109 mounted in an expansion bay or master controller bay module location (not on an EPS-mounted module)
- Alarm currents for 50 devices and above include 20 device LEDs in alarm
- Some applications may require shielded wiring
Related models
- 4100-3110: IDNet 2+2 module, 250 points with four isolating output loops
- 4100-3111: IDNet short-circuit isolating loop output module
Documents
FAQ
Is the 250-point capacity per loop?
No. The 4100-3109 supports 250 addressable points per module, shared across its two isolating output loops.
Can more loops be added?
Yes. Up to two 4100-3111 loop output modules can be mounted on a 4100-3109 in an expansion bay or master controller bay module location, but not on a module mounted on the EPS.
Does the SLC need shielded twisted wire?
No. Shielded or unshielded, twisted or untwisted wire is permitted, although some applications may require shielded wiring.
How far can the loop run?
Up to 4000 ft (50 ohms) with 1 to 125 devices, or 2500 ft (35 ohms) with 126 to 250 devices.