Simplex 4099-9005 — double action addressable manual station with breakglass operation, communicating on IDNet or MAPNET II.
Double action means two deliberate movements raise an alarm: the operator strikes the front hammer to break the glass and expose the recessed lever, which then pulls down like a single action station. The integral module reports the station by its own address.
- IDNet or MAPNET II, one address per station, set by an eight-position DIP switch
- Housing legend FIRE ALARM with a PULL DOWN lever, English
- Red Lexan polycarbonate housing, white raised lettering, white lever
- Housing 5 in. H × 3 3/4 in. W × 1 in. D
- Listed UL, ULC, FM and CSFM to UL Standard 38; NEMA 1 with the 2975-9178 box
- 32°F to 120°F indoor, to 93% RH; screw terminals for 18 AWG to 14 AWG
The 4099-9004 is single action, the 4099-9006 is double action of the push type, and the 4099-9021 is the NO GRIP lever. The 4099-9002 is a separate double action breakglass station carried in Simplex data sheet S14099-0001; Simplex does not publish this station as its replacement.