Sleeping areas such as hotel rooms and dormitories often need a low-frequency alarm at the point of detection. The Simplex 4098-9772 meets that need: it is a TrueAlarm addressable sensor base with a built-in 520 Hz sounder. It uses a single IDNet address and gets communications and sensor power from the IDNet channel.
Key Features
- Low-frequency sounder output: 520 Hz at 85 dBA
- Accepts a TrueAlarm photoelectric, photo/heat or heat sensor (ordered separately)
- Sounder can be supervised and coded by compatible NACs for synchronized temporal, march time or other coding
- Address is set at the base, so it stays with the location when the sensor is removed
- Automatic sensor type identification and magnetic test function
- Integral red LED pulses for normal communication and stays on for alarm or trouble
Specifications
-
Manufacturer: Simplex
-
Part Number: 4098-9772
-
Type: TrueAlarm sensor base with 520 Hz sounder
-
Sounder Output: 520 Hz at 85 dBA
-
Addressing: Single IDNet address (multi-point device)
-
Sounder Power: Separate 24 VDC system power or NAC connection required
-
Mounting: Ceiling, flush mount
-
Certifications: UL 268 and UL 464 certified (sounder also certified to UL 464 as an audible notification appliance); ULC S529; CSFM certified; FM approved
Compatibility
Works with Simplex TrueAlarm sensors on IDNet systems, including the 4007ES, 4010ES and 4100ES control units. Certified for Special Application when used with a compatible NAC circuit.
Documents
FAQ
Is a sensor included?
No. The base requires a TrueAlarm sensor ordered separately: 4098-9714 photoelectric, 4098-9754 photo/heat multi-sensor or 4098-9733 heat sensor.
How is the sounder powered?
The sensor gets power and communications from IDNet, but the sounder needs separate 24 VDC system power or a NAC connection (16 to 32 VDC). Base supervision can be disabled when a supervised NAC powers the sounder for coded outputs.
What electrical box does it mount to?
It requires flush mounting to a 4 in octagonal or 4 in square box 1-1/2 in deep, or a single-gang box 2-1/8 in deep. A 4098-9863 adapter plate is required with 4 in square boxes.
How many panel points does it use?
On 4007ES, 4010ES and 4100ES panels it uses one point per sensor base, with a single IDNet address.