Simplex 4098-9754 is a TrueAlarm multi-sensor that combines a TrueAlarm photoelectric smoke sensor and a fast-acting TrueAlarm thermistor heat sensor in one sensor head. Smoke and heat analog values are sent digitally to the control panel over IDNet two-wire communications, and special point types let the multi-sensor report both values using only one IDNet address.
The host panel processes each sensing element and decides whether conditions are normal, off-normal or alarm. An alarm can come from smoke, from heat, or from TrueSense analysis of the combined smoke and heat activity, which gives earlier detection than either activity alone. The sensor head mounts on a separately ordered TrueAlarm base, including standard, relay, isolator and sounder bases. This item is marked discontinued.
Specifications
| Sensing |
Photoelectric smoke plus thermistor heat, with TrueSense correlation |
| Compatible panels |
Simplex 4007ES, 4010ES, 4100ES and 4100U (4100U needs software revision 11 or higher with multi-point compatible IDNet transmission modules) |
| Communications |
IDNet, 1 address per base |
| Smoke sensitivity |
0.2 to 3.7 %/ft obscuration, selected at the control panel |
| Heat operation |
Fixed 135°F (57.2°C) and/or rate-of-rise at 15°F or 20°F per minute; utility monitoring 32°F to 122°F |
| Air velocity |
0 to 4000 ft/min |
| UL operating range |
32°F to 100°F (0°C to 38°C) |
| Humidity |
10 to 95% RH |
| Certifications |
UL 268 certified; CSFM approved |
Installation notes
- Base is ordered separately: 4098-9792 standard base, 4098-9789 base with remote LED or unsupervised relay connections, 4098-9791 4-wire relay base, 4098-9780 2-wire relay base, 4098-9793 isolator base or 4098-9794 sounder base
- For the 4098-9794 on a flush 4 in. square box, a single gang adapter plate (RACO No. 787 or equal, by others) is required
- The 4098-9832 adapter plate is required to mount the sounder base to surface mounted boxes
- Built-in magnetic test feature for functional testing
- Use with CO sensor bases is covered in data sheet S4098-0052
Related models
- 4098-9714 TrueAlarm photoelectric smoke sensor
- 4098-9733 TrueAlarm heat sensor
- 4098-9764 multi-sensor photoelectric sensor with integral thermal sensor
Documents
FAQ
Is a base included with the 4098-9754?
No. The multi-sensor is ordered separately from its base. Simplex lists standard, relay, isolator and sounder bases for it, such as the 4098-9792 standard base and the 4098-9794 sounder base.
Does it use one or two IDNet addresses?
One. Special point types let the 4098-9754 report both smoke and heat analog data using a single IDNet address.
Which panels support it?
Simplex 4007ES, 4010ES, 4100ES and 4100U panels. The 4100U needs software revision 11 or higher with multi-point compatible IDNet transmission modules.
How is the heat alarm set?
At the control panel: a fixed 135°F (57.2°C) setting and/or a rate-of-rise alarm at 15°F or 20°F per minute. It can also be used for utility temperature monitoring from 32°F to 122°F.