Silent Knight SK-HEAT-ROR-W — white addressable thermal detector combining rate-of-rise response with a 135 °F fixed set point.
All three SK-HEAT-W Series models share one field-programmable thermistor circuit and the panel selects the mode. This is the rate-of-rise ordering number, and without that panel feature it defaults to rate-of-rise plus 135 °F fixed.
- Responds to a rise greater than 15 °F per minute (8.3 °C per minute), fixed alarm point 135 °F (57 °C)
- Rated ambient follows the programmed mode: -4 to 100 °F (-20 to 38 °C) for fixed or rate-of-rise, -4 to 150 °F only if programmed for high heat
- UL 521 certified for 50 ft. spacing, FM approved 25 × 25 ft., FM 3210 response index V2-FAST
- 15 to 32 VDC peak two-wire SLC, 200 µA standby and 2 mA maximum alarm at 24 VDC
- Rotary decimal addressing, walk test with address display, magnet test with the M02-04
- 2.0 in. high and 6.2 in. across in a B300-6 base, 3.4 oz.
The siblings differ by factory setting, not hardware: SK-HEAT-W is 135 °F fixed, SK-HEAT-HT-W is 190 °F high temperature. Bases ship separately: B300-6 or B501-WHITE.