Silent Knight 058950RPS is the replacement printed circuit board for the RPS-1000 intelligent distributed power module. It is the board only, without cabinet or transformer. Installers use it to replace the circuit board in an RPS-1000 on a compatible addressable fire alarm system.
RPS-1000 specifications
| Output power |
6.0 A |
| Programmable circuits |
Six Flexput I/O circuits |
| Relays |
Two Form C, 2.5 A at 24 VDC |
| Notification circuits |
3 A per circuit, 6 A system total |
| Initiation circuits |
100 mA power limited at 24 VDC |
| Standby / alarm current |
40 mA / 160 mA |
| Operating temperature |
32°F to 120°F (0°C to 49°C) |
| Humidity |
10% to 93%, non-condensing |
Features of the RPS-1000
- Class A (Style 6) or Class B (Style 4) SBUS configuration
- Optical isolation of the SBUS with ground loop isolation and transient protection
- Built-in synchronization for System Sensor, AMSECO, Gentex and Wheelock appliances
- Battery charging capacity of 35 AH
- Wiring up to 6,000 ft from the control panel