Siemens SC-LFS-WW-N — Acend series low-frequency sounder, wall mount, white faceplate, no lettering.
The sounder-only member of the Acend low-frequency family: an audible appliance with no strobe element, rated a low-frequency device per UL 464 and suitable for the sleeping areas where NFPA 72 calls for low-frequency signalling. Three DIP switches do the setting up — one picks high or low volume, high by default, the other two select one of four tone patterns. Continuous and T3 hold the UL fire listing; T4 and T4 low power are listed for carbon monoxide, the latter dropping to low power after four minutes.
- Faceplate lettering: NO LETTERING per the Siemens ordering table; part S54361-F16-A2
- 80 dBA high / 77 dBA low, reverberant per UL 464
- 114 mA high volume, 47 mA low volume, on every tone pattern
- 16 to 33 VDC, UL/ULC listed Special Application; 427 g
- Indoor dry only, 32°F to 122°F, 95% RH; UL 464, UL 1638, UL 1971, ULC 525/526
- Single gang, double gang or 4" square box; in/out terminals take #12 to #18 AWG
SC-LFS-WR-N is the red version. The strobe models are SC-LFSS-WW-F and SC-LFSS-WR-F — those are the ones Siemens marks FIRE.