Siemens MS-51 — single-action conventional manual fire alarm box, ordered under Siemens part number 500-620503 as Manual Station N.O. SPST.
Single action means one movement raises the alarm: the pull-down lever releases a spring-loaded contact and locks down, visibly showing which box was operated. It is a conventional device wired into a zone loop rather than an addressable one.
- Part number 500-620503, described by Siemens as Manual Station N.O. SPST
- Normally open SPST alarm contact rated 0.75 A at 28 VAC or VDC
- Optional auxiliary normally closed contact and key switch, each at the same rating
- Non-code type, molded polycarbonate, matte red with raised white lettering
- Reset by opening the hinged cover with an Allen key; no break rod required
- Surface or semi-flush mounting; meets ADA guidelines; UL Certified, FM, CSFM and NYCFD approved
The MS-501, part number 500-620522, is the double action station in the same series. The MS-151 is a separate catalogue number, 500-688458, also described as Manual Station N.O. SPST, and the MS-EP, 500-694511, is the explosion-proof version.