Siemens HMS-D — addressable dual-action manual fire alarm box, catalogue number 500-033400.
A dual-action station needs two separate motions: the lever marked PUSH IN must be operated before the pull-down lever will release, which is what separates it from the single-action HMS-S. A microcomputer chip inside holds the station address and communicates in both directions with the panel, so the panel identifies the individual box.
- Current draw 0.9 mA, active or standby; two-wire, polarity insensitive
- Electronic address programming to non-volatile memory using the Model DPU programmer
- Lever locks down until reset by opening the cover with an Allen key; no break rods
- Surface mounting on the SB-5R box or semi-flush in a single-gang switch box
- Indoor and dry: 32° to 100°F, 0 to 93% humidity non-condensing
- UL certified, FM 3015946, CSFM 7150-0067:0036, USCG 161.002/60/0; ADA compliant
It operates with FireFinder-XLS and FS-250 panels through the DLC or FS-DLC device loop card. HMS-S (500-033200) is the single-action station in the same housing; HMS-DE and HMS-DP are the Spanish and Portuguese versions.
FAQ
Which panels does the HMS-D work with?
Siemens Fire Safety panels, including the Siemens Modular panel and the Siemens 50-point, 252-point and 504-point addressable FACPs.
How is the address set?
With the Siemens DPU device programmer/test unit, which writes the address electronically into the station's non-volatile memory, so there are no mechanical address switches.
How is it reset after use?
The pull-down lever stays locked down until the station is reset by opening the hinged cover with an Allen key and then closing and locking it. The LTP reset tool package contains two tools.
Can it be surface mounted?
Yes. It can be surface or semi-flush mounted; the SB-5R is the surface mounting box.