Siemens FJ-303 — P/N 500-690975, a field-mounted firefighters telephone jack with flying leads.
A firefighters phone riser puts a jack at each stair landing, elevator lobby and floor so a portable handset can be plugged in anywhere and talked back to the command station. The FJ-303 is the single-jack station in that riser.
- Single telephone jack with flying leads, for field mounting
- Connects to a TZC-8B telephone zone card (FireFinder XLS, Desigo Fire Safety Modular, Cerberus PRO Modular) or a ZCT-8B (MXL)
- Field wiring 18 AWG minimum to 14 AWG maximum, per NEC Article 760
- End-of-line resistor 10 kΩ, 1/4 W, 5% — Siemens P/N 140-820196
- Use only with handset models PT-303, PT-304, PFT or PFT-P
Two installation traps. Leave the 10 kΩ EOL resistor fitted only in the last station on the zone and remove it from every other FJ-303. In Canada, remove all supplied EOLs and use EOL P/N 140-034726 mounted in a Model EL-33.