Potter PFC-4064 RB — replacement main board assembly for the Potter PFC-4064 conventional fire alarm control panel.
When a PFC-4064 is lost to a surge or wiring fault, the enclosure, door and field terminations are usually intact and only the board needs to change. Potter sells that board on its own as item 3992363, against item 3992360 for the complete panel in its cabinet, so a service call need not become a re-installation.
- Six programmable input circuits, Class A or B, expandable to 192 with IDC-6 cards
- Four power-limited NACs rated 3.0 A each, with strobe sync
- 5.0 A 24 VDC supply; NAC plus auxiliary load must not exceed 5.0 A
- One 1.0 A auxiliary output; four Form C relays
- 4 × 20 LCD, P-Link RS-485 bus, Ethernet, 4,000-event log
- AC input 120/240 VAC 50/60 Hz, 2.5 A max; battery circuit 7–55 AH
- UL-864, NFPA-70, NFPA-72; indoor only, 32° to 120°F
Board only — no cabinet, door or batteries. Budget time to re-enter the site program and re-test the system afterwards.