The PAD300-DUCTR is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors
Air sampling is accomplished by two (2) tubes which protrude into the duct. An exhaust tube of one (1) standard length (7”) is supplied in the installation kit with the smoke duct unit.
Once the duct width has been determined, the air intake sampling tubes must be ordered.
Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct.
Mounting the duct smoke unit is accomplished by the use of a template and two (2) sheet metal screws, which are provided.
Mounting can be achieved without the removal of the clear cover which is secured by four (4) capture screws.
Features
- Detects Smoke in Building HVAC Ducts
- Ships Complete with Housing and Head
- Compatible with Addressable IPA and AFC/ARC Series Panels
- SLC Class A, Class X & Class B
- Installation Without Removing the Head
- Certified Air Velocity of 300 to 4,000 ft/minute
- No Screens or Filters in Housing
- Durable Plastic Enclosure and Clear Cover
- Integrated Cover Tamper Switch
- Utilizes Simple Snap in Sampling Tubes STN Series
- One Form C Relay
- UUKL Certified for Smoke Control
- Compatible with Supervised PAD100-DRTS Remote Test Switch, MS-RA, MS-KA/R,
- MS-KA/P/R Remote Indicators
- Product includes 5-year warranty
Documents
FAQ
Is the detector head included?
Yes. The PAD300-DUCTR ships complete with the housing and the PAD300-DD photoelectric head. The air intake sampling tube must be ordered separately to suit the duct width.
Which sampling tube should I order?
Sampling tubes come in 2.5 ft, 5 ft and 10 ft lengths and are cut to fit the duct. A 7 in. exhaust tube is supplied in the installation kit.
What air velocity does it support?
300 to 4,000 ft/min.
What is the relay rating?
The Form C relay is rated 8 A at 30 VDC and 10 A at 120 or 250 VAC.