Potter PAD200-DUCTR — analog addressable duct smoke detector, supplied complete with housing and a PAD200-DD photoelectric head, and carrying one form C relay.
Two tubes protruding into the duct sample the air moving through it, and mounting uses a template and two screws without removing the clear cover. The R is the relay, not a mounting or protocol variant: Potter lists the unit as an Analog Addressable Duct Detector W/Relay.
- 24 VDC, 500 µA draw; the relay-less PAD200-DUCT draws 300 µA
- Relay contacts rated 8 A at 30 VDC, 10 A at 120 VAC and 10 A at 250 VAC
- Photoelectric head fixed at 2.5%/ft; rated air velocity 100 to 4,000 ft./min.
- 32 to 120 °F, 10% to 85% RH non-condensing; 13 1/2 in. L × 4 1/2 in. W × 2 1/4 in. H, 2 lb
- SLC Class A, X and B; cover tamper switch; UL 268A and UUKL certified for smoke control
The 7 in. exhaust tube ships in the kit; intake sampling tubes are ordered separately once duct width is known — STN-2.5, STN-5, STN-10. PAD200-DD is the bare head alone, no housing or base. Supervised accessories: PAD100-DRTS, MS-RA, MS-KA/R, MS-KA/P/R.
Documents
FAQ
Are sampling tubes included?
No. The 7 in. exhaust tube comes in the installation kit, but the intake sampling tube is ordered by duct width in 2.5 ft, 5 ft or 10 ft lengths and cut to fit.
What is the difference from the PAD200-DUCT?
The R model adds one Form C relay and draws 500 µA; the PAD200-DUCT has no relay and draws 300 µA.
What air velocity is it rated for?
100 to 4,000 ft per minute, at 32°F to 120°F.
Does it need to be opened to install?
No. It mounts with a template and two sheet metal screws, and the head can stay in place during installation.