Potter LOC-1000 — local operator console for the Potter IPA-4000V voice evacuation fire alarm system, used to control the system, generate live voice and run emergency communication (ECS) from a remote location.
The LOC-1000 communicates with the IPA-4000V over an RS-485 P-Link connection and gives common indication of alarm, supervisory, trouble and other system status. All call, individual zone paging and ECS activation can be done directly at the console. It is built from three modules: the LOC-RA6500R remote annunciator, the SB-8 switch board and the VM-1000 voice module.
Specifications
| Model |
LOC-1000 |
| Host panel |
Potter IPA-4000V |
| Communication |
RS-485 via P-Link |
| Maximum per system |
31 consoles |
| Modules |
LOC-RA6500R annunciator, SB-8 switch board, VM-1000 voice module |
| SB-8 controls |
8 programmable buttons, All Call, ECS Reset and Control |
| Addressing |
5-position DIP switch, addresses 1–31 |
Installation notes
- The LOC-RA6500R and VM-1000 each take their own address; they must not share the same address
- The LOC-RA6500R can communicate with and be powered from a PSN-1000; the console has a bracket to mount an optional PSN-1000
- All terminals are power limited and must be wired per NFPA 70 and NFPA 72
Related models
- VM-1000: voice module used in the console
- PSN-1000: intelligent notification power expander that can power the console
Documents
FAQ
Which panel does the LOC-1000 work with?
The Potter IPA-4000V, communicating over an RS-485 P-Link connection.
How many consoles can be used?
A maximum of 31 LOC-1000 consoles can be employed.
What can the operator do at the console?
All call, individual zone paging and ECS activation, using the SB-8 with 8 programmable buttons, an All Call button and an ECS Reset and Control button.
Can it have its own power supply?
Yes. The console includes a bracket for an optional PSN-1000, and the LOC-RA6500R can communicate with and receive power from the PSN-1000.