Potter EVAX-50 is a self-contained 50 W voice evacuation panel that combines an amplifier, tone generator, digital message repeater and supervisory interface. It works with a UL certified fire alarm control panel (FACP) to make a voice evacuation alarm system: the FACP provides all initiating circuits and a signaling circuit to the EVAX, and the EVAX handles the speaker side.
The EVAX supervises itself and its speaker lines. In normal standby the panel supervisory circuit is connected to a matching end-of-line resistor; an internal failure or a speaker line fault opens a contact so the FACP reports an open fault on that circuit. The unit runs on 120 VAC with its own battery charger, and the alarm tone, automatic message repeats and the 6-hour AC power failure reporting delay are field configurable.
Specifications
| Output |
50 W to the speaker circuit |
| Speaker voltage |
25 or 70 VRMS, jumper selected (25 V factory set) |
| AC power |
120 VAC, 60 Hz |
| Batteries |
Two 12 V batteries in series; 24 V 7 Ah minimum, 18 Ah maximum |
| Speaker wiring |
Class B, or Class A (Style Z) with return on TB1-7 and TB1-8 |
| Built-in features |
Amplifier, tone generator, digital message repeater, microphone |
| Enclosure |
Surface or semi-flush backbox with hinged, key-locked door |
Installation notes
- Install in a clean, dry location free of vibration; remove electronics before drilling or punching the enclosure
- Use the end-of-line resistor value the FACP manufacturer specifies for its indicating appliance circuit
- Connect batteries only after AC power is on; battery wiring is non-power-limited and needs 1/4 in. spacing from power-limited wiring
- If the microphone is not installed, set switch SN2-8 to OFF
- Install per NFPA 70, NFPA 72 and NFPA 101
Related models
- EVAX-25: 25 W version
- EVAX-100: 100 W version
Documents
FAQ
Does the EVAX-50 need its own fire alarm panel?
Yes. It is designed to work with a UL certified FACP, which provides the initiating circuits and a signaling circuit to the EVAX.
What speaker voltage does it use?
Speakers can be 25 or 70 VRMS, selected by jumper; 25 V is the factory setting.
What batteries does it need?
Two 12 V batteries in series, from 24 V 7 Ah minimum up to 18 Ah maximum on the EVAX 25 and EVAX 50.
How are faults reported to the FACP?
The EVAX supervises itself and its speaker lines. A fault opens the supervisory contact, and the FACP reports it as an open fault on that circuit.