Notifier RP-2002 — a six zone agent release control panel, not an ordinary fire alarm panel.
Its purpose is to discharge a suppression agent. Notifier designs it to NFPA 12, 12A, 12B and 2001, covering carbon dioxide, Halon 1301, Halon 1211 and clean agent, in single or dual hazard configurations. Detection uses conventional circuits; the release logic, timers and abort handling are the point.
- Six Class B initiating device circuits, zones 1 to 5 on TB4 and zone 6 on TB6; Class A via N-CAC-5X
- Four outputs, each programmable as a notification appliance circuit or a releasing circuit, within 7.0 A total
- Adjustable pre-discharge, discharge and waterflow timers, cross-zone interlock, programmable abort
- Disable and enable control per input and per output zone, with extensive transient protection
- Listed to UL 864 9th Edition, FM approved, CSFM 7165-0028:0245; stated to meet IBC seismic
It ships with back box, power supply and manual; agent solenoids, NBG-12LR agent release pull stations, batteries of 7 to 26 Ah and the SEISKIT-COMMENC seismic kit are not. RP-2002E is the 220/240 VAC version.