Notifier RP-2001 — six-zone releasing control panel for single and dual hazard deluge and preaction sprinkler systems.
This is a water-based releasing panel, not a general fire alarm panel and not an agent release panel. Each of its four output circuits is programmable as either a notification appliance circuit or a releasing circuit. It supervises all wiring, AC voltage and the battery, and accepts conventional detectors, pull stations, waterflow and tamper switches.
- Designed to sprinkler standards NFPA 13, 15 and 16, plus NFPA 72; cross-zone double-interlock
- Six programmable Class B initiating circuits, Class A via the N-CAC-5X
- Adjustable waterflow discharge timer and two soak timers
- 7.0 amps total 24 VDC output, 300 mA regulated maximum per NAC
- Three programmable Form C relays, 2 A at 30 VDC resistive
- UL 864 9th edition, UL S635, FM approved
The panel includes its backbox and power supply; batteries, the DP-51050 dress panel and TR-CE trim ring are ordered separately, as are the solenoids. The RP-2002 is the agent release version, built to NFPA 12, 12A, 12B and 2001, with abort. RP-2001E is 240 VAC and RP-2001C the ULC model.
Documents
FAQ
What systems is the RP-2001 for?
Single and dual hazard deluge and preaction sprinkler systems, designed to NFPA 13, 15 and 16. The RP-2002 is the agent release version.
Can the circuits be Class A?
Yes, with the optional N-CAC-5X Class A converter module for the initiating and output circuits.
How much output current is there?
7.0 A total at 24 VDC, with 300 mA regulated maximum per NAC; total resettable, non-resettable and output power must not exceed 7.0 A.
What optional parts are available?
The DP-51050 red dress panel, the TR-CE red trim ring for semi-flush mounting, the N-CAC-5X Class A converter and the 4XTM municipal box transmitter.