The Notifier NMM-100-10 Ten-Input Monitor Module is an interface between a FireWarden series control panel and normally open contact devices in intelligent alarm systems such as pull stations, security contacts, or flow switches
The first address on the NMM-100-10 is set from 01 to 90 and the remaining modules are automatically assigned to the next nine higher addresses. Provisions are included for disabling a maximum of two unused addresses.
The supervised state (normal, open, or short) of the monitored device is sent back to the panel. A common SLC input is used for all modules, and the initiating device loops share a common supervisory supply and ground — otherwise each monitor operates independently from the others.
Each NMM-100-10 module has panel-controlled green LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
NOTE: Unless otherwise specified, the term NMM-100-10 is used in this data sheet to refer to both the NMM-100-10 and the NMM100-10A (ULC-listed version).
Features
• Listed to UL Standard 864, 9th edition.
• Ten addressable Class B or five addressable Class A initiating device circuits.
• Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²) plug-in terminal blocks.
• Status indicators for each point.
• Unused addresses may be disabled.
• Rotary address switches.
• Class A or Class B operation.
• Flexible mounting options.
• Mounting hardware included.
Specifications
Standby current: 3.5 mA (SLC current draw with all addresses used; if some addresses are disabled, the
standby current decreases).
Alarm current: 55 mA (assumes all ten LEDs solid ON).
Temperature range: 32°F to 120°F (0°C to 49°C) for UL applications; –10°C to +55°C for EN54 applications.
Humidity: 10% to 85% noncondensing for UL applications;
10% to 93% noncondensing for EN54 applications.
Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x 1.25" (31.75 mm) deep.
Shipping weight: 0.76 lb. (0.345 kg) including packaging.
Mounting options:
– CHS-6 chassis: Up to 6 modules.
– BB-25 cabinet: Up to 6 modules.
– BB-XP cabinet: One or two modules.
Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).
Power-limited circuits must employ type FPL, FPLR, or FPLP cable as required by Article 760 of the NEC.
NMM-100-10 supports both Class B and Class A wiring;
remove shunt for Class A operation.
Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent.
Maximum IDC wiring resistance: 1500 ohms.
Maximum IDC voltage: 10.2 VDC.
Maximum IDC current: 240 μA.
Agency Listings and Approvals
The listings and approvals below apply to the NMM-100- 10 Ten-Input Monitor Module. In some cases, certain modules or applications may not be listed by certain approval
agencies, or listing may be in process. Consult factory for latest listing status.
• UL Listed: S635
• ULC Listed: S635 (NMM-100-10A)
• CSFM approved: 7300-0028:256
• FM approved